Information for Wolverhampton Energy from Waste Plant, Crown Street, Wolverhampton
Status: ExistingPlanning Region: West Midlands
Planning Sub-Region: West Midlands Met Districts
Operator: North Midlands Operations Ltd (NMOL) - previously run by MES Environmental Limited
Capacity: 118,000
Campaign Group(s): Contact coordinator@ukwin.org.uk to be put in touch with those opposing this development.
Notes: (Entry updated 2019-06-06)
Waste management for England 2024: Operational (Environment Agency)
Uses data from 2024 Waste Data Interrogator - Version 2 released by the Environment Agency under the Environment Agency Conditional Licence. © Environment Agency copyright
Permit: HP3349QK
| Date First Permitted | Operator Name | Site Name | Site Address | Type | Permitted Capacity (tonnage) | Tonnage Incinerated in 2006 | Tonnage Incinerated in 2007 | Tonnage Incinerated in 2008 | Tonnage Incinerated in 2009 | Tonnage Incinerated in 2010 | Tonnage Incinerated in 2011 | Tonnage Incinerated in 2012 | Tonnage Incinerated in 2013 | Tonnage Incinerated in 2014 | Tonnage Incinerated in 2015 | Tonnage Incinerated in 2016 | Tonnage Incinerated in 2017 | Tonnage Incinerated in 2018 | Tonnage Incinerated in 2019 | Tonnage Incinerated in 2020 | Tonnage Incinerated in 2021 | Tonnage Incinerated in 2022 | Tonnage Incinerated in 2023 | Tonnage Incinerated in 2024 | Tonnage Incinerated in 2022 | Tonnage Incinerated in 2023 | Tonnage Incinerated in 2024 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 01/12/2005 | North Midlands Operations Ltd | Wolverhampton Energy from Waste Facility | Waste to Energy Plant,Crown Street,Wolverhampton,West Midlands WV1 1QB | Municipal and/or Industrial & Commercial | 118,000 | 100,773 | 104,356 | 107,231 | 109,991 | 108,817 | 106,088 | 109,992 | 109,280 | 110,132 | 104,164 | 110,759 | 112,213 | 110,298 | 114,412 | 114,425 | 111,937 | 109,917 | 97,582 | 88,372 | 109,917 | 97,582 | 88,372 |
Waste management for England 2023 & 2024: Waste received
2023: Uses data from 2023 Waste Data Interrogator - Version 2 released by the Environment Agency under the Environment Agency Conditional Licence. © Environment Agency copyright
2024: Uses data from 2024 Waste Data Interrogator - Version 2 released by the Environment Agency under the Environment Agency Conditional Licence. © Environment Agency copyright
Permit: HP3349QK
Form: Solid
EWC Waste Desc: mixed municipal waste
Waste Code: 20 03 01
Fate: Incineration
SOC Category: 10 - Mixed ordinary wastes
SOC Sub Category: Household and similar wastes
| Recorded Origin | Origin WPA | Origin Region | R and D code | Tonnes Received (2023) | Tonnes Received (2024) |
|---|---|---|---|---|---|
| Wolverhampton | Wolverhampton | West Midlands | R01 | 67,587 | 53,799 (-20%) |
| Wolverhampton | Wolverhampton | West Midlands | D10.01 | 17,744 | |
| North Northamptonshire | Northamptonshire | East Midlands | R01 | 13,238 | |
| North Northamptonshire | Northamptonshire | East Midlands | D10.01 | 5,370 | |
| Northamptonshire | Northamptonshire | East Midlands | R01 | 29,458 | |
| Dudley | Dudley | West Midlands | R01 | 408 |
Environment Agency 2024 & 2025 Pollution Inventory: Substances
2024: Uses data from the Pollution Inventory 2024 released by the Environment Agency under the Open Government License.
2025: Uses data from the Pollution Inventory 2025 snapshot from April 2025 released by the Environment Agency under the Open Government License. The data may change in the final version.
Permit: HP3349QK
SITE ADDRESS: Waste to Energy Plant Crown Street
ROUTE NAME: Air
| SUBSTANCE NAME | QUANTITY RELEASED (kg) (2024) | QUANTITY RELEASED (kg) (2025) | METHODNAME (2024) | METHODNAME (2025) | METHODTEXT | METHODDESCRIPTION (2024) | METHODDESCRIPTION (2025) |
|---|---|---|---|---|---|---|---|
| Carbon dioxide | 83,323,000 | 72,457,000 (-13%) | Measured (For all years) | Measurement method prescribed by us in an operating permit or licence for the facility (For all years) | |||
| Carbon Dioxide From Qualifying Renewable Fuel Sources | 45,077,000 | 32,919,000 (-27%) | Estimated | Calculated | Other calculation method | ||
| Ammonia | 1,972 | 1,120 (-43%) | Measured (For all years) | Measurement method prescribed by us in an operating permit or licence for the facility (For all years) | |||
| Dioxins and furans (PCDDs/PCDFs) - as ITEQ | 0 | Measured | Measurement method prescribed by us in an operating permit or licence for the facility | ||||
| Dioxins and furans (PCDDs/PCDFs) - as WHO TEQ | 0 | Measured | Measurement method prescribed by us in an operating permit or licence for the facility | ||||
| Polychlorinated biphenyls (PCBs) - as WHO TEQ | 0 | Measured | Measurement method prescribed by us in an operating permit or licence for the facility | ||||
| Chromium | 78.63 | Measured | Measurement method prescribed by us in an operating permit or licence for the facility | ||||
| Mercury | 2.41 | Measured | Measurement method prescribed by us in an operating permit or licence for the facility | ||||
| Arsenic | 2.15 | Measured | Measurement method prescribed by us in an operating permit or licence for the facility | ||||
GHG Performance in 2023
Uses data from Pollution Inventory 2023 extract and Annual Peformance Reports submitted by operators and released by the Environment Agency under the Open Government License
Permit: HP3349QK
| Permitted capacity (ktpa) | Total waste combusted | CO2 (kg) | CO2 per tonne (kg) | CO2 Source |
|---|---|---|---|---|
| 118 | 98,039 | 92,352,738 | 942 | Annual Performance Report |
APR Summary 2024 & 2025
Details taken or derived from the Annual Performance Report submitted by the operator
Permit: HP3349QK
| Entry | Value (2024) | Value (2025) | Notes (2024) | Notes (2025) |
|---|---|---|---|---|
| Plant Size TPA | 118,000 | 118,000 | Wolverhampton Energy from Waste Facility (For all years) | |
| Plant Size MWth | 33.97 | |||
| Plant Size MWe | 6.90 | |||
| Power Generated Year Total | 21,096.00 | 35,726.00 (+69%) | ||
| Power Generated kWh per tonne | 238.72 | 399.47 (+67%) | ||
| Power Exported Year Total | 11,964.00 | 29,515.00 (+147%) | ||
| Power Exported kWh per tonne | 135.38 | 330.02 (+144%) | ||
| Power Imported Year Total | 0.00 | 1,469.70 | ||
| Power Imported kWh per tonne | 16.43 | |||
| Parasitic Load Year Total | 0.43 | 0.21 (-51%) | ||
| Thermal Energy Exported Year Total | 0.00% | 0.00 | ||
| Total Waste Received Year Total | 90,217.00 | 88,444.00 (-2%) | ||
| Total Waste Combusted Year Total | 8,837,200.00% | 89,433.00 | Household / Local Authority (79.37%) | Household / Local Authority (80.99%) |
| NCV Year Total | 8.32 | |||
| Permit Breaches Year Total | 5.00 | 6.00 (+20%) | ||
| Annual CO2 Mass | 83,323.00 | 72,456.61 (-13%) | CEMS CO2 Monitoring (For all years) | |
| Annual CO2 Mass Per Tonne | 0.94 | 0.81 (-14%) | ||
| Annual CO2 Mass Per Mwh | 6.96 | 2.45 (-65%) | ||
| Annual N2O Mass | 8.80 | 6.17 (-30%) | CEMS CO2 Monitoring (For all years) | |
| Total CO2 N2O | 74,092.13 | |||
| Biogenic CO2 Percentage | 0.54 | 0.56 (+4%) | Waste compositional analysis. | Waste compositional analysis by NCV. |
| Biogenic Percentage NCV | 0.54 | 0.56 (+4%) | Waste compositional analysis. | Waste compositional analysis by NCV. |
| Biogenic Percentage Mass | 0.54 | 0.68 (+26%) | In accordance with Ofgem-approved fuel measurement and sampling plan. | Waste compositional analysis by mass. |
Entry on WikiWaste:
https://wikiwaste.org.uk/index.php/Wolverhampton_EfWAnnual Performance Report files:
210-AnnualPerformanceReport-2018.pdf210-AnnualPerformanceReport-2019.pdf
210-AnnualPerformanceReport-2020.xlsm
210-AnnualPerformanceReport-2021.xlsm
210-AnnualPerformanceReport-2022.xlsm
210-AnnualPerformanceReport-2023.xlsm
210-AnnualPerformanceReport-2024.xlsm
210-AnnualPerformanceReport-2025.xlsm
Permit Variation files:
210-PermitVariation-2023.pdfPermit Variation Decision files:
210-PermitVariationDecision-2023.pdfEnvironment Agency Compliance Assessment Reports
Click here to see the incinerator compliance documents for existing English incineratorsStandard notice:
UKWIN (and therefore the UKWIN map) focuses on Municipal Waste Incinerators, whereas our colleagues at Biofuelwatch focus on biomass projects. If you are interested in biomass incinerators (including waste wood plants) over 20MW then please see the Biofuelwatch map of UK Biomass Power Stations. Those concerned about biomass plants, including waste wood plants, should email Biofuelwatch at biofuelwatch[at]gmail.com.Please be aware: There is always room for improvement, so please send updates to coordinator@ukwin.org.uk. Existing Incinerator means a facility that is operational or under construction/commissioning. A Potential Incinerator is a facility where there is a proposal for an incinerator (e.g. planning application or planning consent) or other reason to believe an incinerator might be built/proposed in the future. A Prevented Incinerator is something which used to be a proposal or expected incinerator which we do not believe is currently being progressed (e.g. because the project was cancelled, planning permission refused, or years have gone by since the permission was granted without any progress) - in some cases a facility marked as prevented is being progressed without us being aware or is subsequently revived. Capacity is usually the permitted or maximum advertised capacity of the facility.